YVCV-U, YVCV-R, NYCY

Place of use

In door installations, in cable ducts, outdoor and underground for power stations, industrial plants and switching stations as well as local supply systems if increased protection is necessary. In case of mechanical damage the screen prevents any demage due to power leak to the surrounding area. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • PVC inner sheath.
  • Concentric screen.
  • Copper tape as binder.
  • Polyester tape.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-34000001 1x1.5/1.5 10.5 120 1000 12.1000 - 25
28-34000002 1x2.5/2.5 11.0 150 1000 7.4100 - 34
28-34000003 1x4/4 12.0 200 1000 4.6100 - 45
28-34000004 1x6/6 12.5 250 1000 3.0800 - 57
28-34000005 1x10/10 13.5 350 1000 1.8300 - 78
28-34000006 1x16/16 15.0 450 1000 1.1500 127 103
28-34000007 1x25/16 16.5 600 1000 0.7270 163 137
28-34000008 1x35/16 17.5 700 1000 0.5240 195 169
28-34000009 1x50/25 19.0 950 1000 0.3870 230 206
28-34000010 1x70/35 21.0 1250 1000 0.2680 282 261
28-34000011 1x95/50 23.5 1650 1000 0.1930 336 321
28-34000012 1x120/70 25.5 2100 1000 0.1530 382 374
28-34000013 1x150/70 27.0 2400 1000 0.1240 428 428
28-34000014 1x185/95 30.0 3000 1000 0.0991 483 494
28-34000015 1x240/120 33.5 3850 1000 0.0754 561 590

Technical Info